| Available watt densities | 10, 20, 30, 39, 49, 66 W/m @10°C 3, 6, 9, 12, 15, 20 W/ft @50°F |
| Max Continuous Operating Temperature | 240°C (464°F) |
| Max Exposure Temp Intermittent (power-on or off) | 250°C (482°F) |
| Continuous power-off | 240°C (464°F) |
| Minimum installation temperature | -60°C (-76°F) |
| T-Rating: | |
| 3, 6, 9, 12, 15-2 | T3 200°C (392°F) |
| 15-1 and 20-1 | T2D 215°C (419°F) |
| 20-2 | T2C 230°C (446°F) |
| Based on stabilized design | T3 to T6 |
USX Heat tracing Cable
Self-Regulating Heating Cable
USX self-regulating heat tracing is specifically engineered for critical process maintenance and freeze protection applications where ultra-high temperature ratings are required. USX enables the use of ambient sensing controls for applications with continuous exposure temperatures up to 240°C (464°F). Constructed using Thermon’s unique and proven monolithic co-extrusion process, USX advances self-regulating heat tracing technology to the ultimate frontiers of performance and reliability.
The heat output of USX heat tracing varies in response to the surrounding temperature. Variations in the ambient temperature or heat lost through the thermal insulation are compensated for automatically along the entire length of a heat-traced pipe.
FEATURES
Higher continuous operating and exposure temperatures 240°C (464°F), creating new possibilities for reliable self-regulating technology
Thermon’s unique and proven monolithic co-extrusion technology provides superior performance and reliability
Enhanced safety and ease of installation for electric heat tracing systems for high temperature applications
SPECIFICATIONS